MX341 Blue


Sensing Input
Voltage
190-264V ac max, 1 phase, 2 wire
Frequency
50-60 Hz nominal

Power Input
Voltage
140-220V ac max, 3 phase, 3 wire
Current
3A/phase
Frequency
100-120 Hz nominal


Output
Voltage
Max 120V dc
Current
Current continuous 2.7 A
Intermittent 6A for 10 secs.
Resistance
15 ohms min.
Regulation
+/- 1%
Thermal drift
0.03% per oC change in AVR ambient
SOFT START RAMP TIME
3 seconds

Typical system response
AVR response
10 ms
Filed current to 90%
80 ms
Machine Volts to 97%
300 ms
External voltage adjustment
 +/-10% with 1 k ohm 1 watt trimmer

Uuder frequency protection
Set point
95% Hz
Slope
170% down to 30 Hz
Unitpower dissipation
12 watts maximum

Analogue voltage
Maximum input
±5 Vdc
Sensitivity
1V for 5% Generator Volts (adjustable)
Input resistance
1k ohm

Quadrature droop input
10 ohms burden
Max. sensitivity: 0.07 A for 5% droop 0PF
Max. input: 0.33 A


Environmental
Vibration
20-100 Hz,50mm/sec; 100Hz – 2kHz, 3.3g
Operating temperature
-40 to +70 Deg. C
Relative humidity 0-70℃
95%
Storage temperature
Storage temperature -55 to +80C