LXC7220C

 LXC3110 generator controller power plant automation controller integrating digital, intelligent and network technology, diesel generator sets for a single automation and monitoring system, automatic generator start / stop, data measure and alarming, and "three remote" (to be equipped with RS485 module) function. Controller with large-screen LCD display, Chinese, English, Spanish and Russian optional interface with operation easy and reliable operation. Parameters to achieve a variety of precision measurement, setpoint adjustment, timing and threshold setting and other functions, the controller of all parameters can be adjusted from the controller front panel, or by using a PC via USB, RS232 interface programming, adjustment and monitoring. Its compact, simple wiring, high reliability, and can be widely used in all types of generator automation systems
Main features:
1,132x64 LCD with backlight, optional language interface (Chinese, English, Spanish and Russian), push-button operation;
2,Adapt to 3 phase 4 wire, single phase 2 wire, 3 phase 3 wire and 2 phase 3 wire (120/240V), 50/60Hz power supply;
3,The controller Can measure and display 3-phase voltage, 3-phase current, frequency, and power.
4,For mains: Over/under voltage, lack of phase; for generator: over/under voltage, over/under frequency, over current;
5,Precision measure and display engine parameters: Coolant temperature, oil pressure, fuel quantity, charger voltage, and depending on the setting for effective protection of the engine, to avoid accidental damage to the engine;
6,Control protection: Automatic start/stop, switch on/off (ATS control) and fault display;
7,With ETS, idle control, pre-heat control, acceleration and deceleration control, all are relay output;
8,Parameters setting: Allow user to modify parameters and store them in internal EEPROM, which cannot be lost even when power off. All the parameters can be adjusted from the front panel, or by PC via USB;
9,Types of temperature and pressure sensor can be directly used and user defined;
10,Conditions of crank disconnect can be selected.(magnetic pickup, oil pressure, generator);
11,Power supply range is (8~35)VDC, accommodating to different starting voltage;
12,Modular design, flame retardant ABS shell, plug-in terminals, embedded mounting, compact structure, easy installation.
 

ItemsContents
Working VoltageDC8. 0V to 35. 0V, Continuous Power Supply.
Overall Consumption<3W(Standby mode: ≤2W)
AC voltage Input:  
3 Phase 4 Wire 15V AC - 360 V AC (ph-N)
2 Phase 3 Wire 15V AC - 360 V AC (ph-N)
Single phase 2 Wire 15V AC - 360 V AC (ph-N)
3 Phase 3 Wire 30V AC - 620 V AC (ph-ph)
Alternator Frequency50 Hz /60Hz
Speed Sensor Voltage1.0V to 24V (effective value) 
Speed Sensor Frequency10,000 Hz (max)
Start Relay Output5A  DC28V power supply 
Programmable Relay Output 15A  DC28V power supply
Programmable Relay Output 25A  DC28V power supply
Programmable Relay Output 35A  DC28V power supply
Programmable Relay Output 45A  AC250V voltage-free output 
Programmable Relay Output 5 5A  AC250V voltage-free output 
Overall Dimensions 143mm x 115mm x41mm
Panel Cutout110mm x 90mm
CT Secondary Current5A (rated) 
Working Condition Temperature: (-25~70)ºC;      Humidity: (20~93)%RH
Storage ConditionTemperature: (-25~70)ºC 
 IP55:When waterproof rubber seal installed between the controller and panel fascia.
Protection Level IP42:When waterproof rubber seal is not installed between the controller and panel fascia.
 Object: input/output/power
Insulation IntensityQuote standard: IEC688-1992
 Test way: AC1.5kV/1min leakage current:3mA