Sensing Input | |
Voltage | 220/400VAC,1 phase 2wire |
Voltage Build-up | Residualvolts at AVR teminal>5VAC |
Power Input | |
Voltage | 180-240VAC,1 phase2wire |
External Vdits Adjustment | ±7%with 1k Ω1wait trimmer |
Output | |
Voltage | Max.90VDC@240V ACinput |
Sotf Start Ramp Time | 3sec. |
Current |
Continuous 6A
Intermittent 12A for 10SEE
|
Unit Power Dissipation | Max.8Watt |
EMI Suppression | Intermal Electromagnetic Interference Filtering |
Resistance | Min.10Ω Max.100Ω |
Thermal.Drift | 0.05%per°C chage in AVR ambient |
Under Frequency Protection | 60Hzsystem presets knee pointat 57Hz |
(Factory Settings) | 50Hzsystem presets knee point at 47Hz |
Volts | Regulation<±0.5%(with 4%engine goveming) |