Specifications
1.Can be used in Parallel Operation
2.16 ADC Current Output
3.Suitable Frequency 400 Hz
4.Soft Start Voltage Ramping
2.16 ADC Current Output
3.Suitable Frequency 400 Hz
4.Soft Start Voltage Ramping
Specification:
AVR EA16
· < ±0.5% Regulation
· Suitable for brushless type generator Sensing Input 170~510 VAC
· Can be used in Parallel Operation
·16 ADC Current Output
· EA16 Suitable Frequency 50/60 Hz , EA16-400Hz Suitable Frequency 400 Hz
· Soft Start Voltage Ramping
· Load CT Current Compensation, Analogue
Voltage Input
Model NO.
|
EA16
|
EA16-400Hz
|
Sensing Input
|
Voltage 170~510 VAC Single Phase 2 wire
|
Voltage 170~510 VAC Single Phase 2 wire
|
Frequency 50/60 Hz
|
Frequency 400 Hz
| |
Power Output
|
Voltage 60~300 VAC Single Phase 2 wire
Max. 90 VDC @ 240 VAC input |
Voltage 60~300 VAC Single Phase 2 wire
Max. 90 VDC @ 240 VAC input |
Input
|
Current Continuous 16A, Intermittent 20A for 10 Sec.
Resistance Min. 6Ω @ 35 VDC |
Current Continuous 16A, Intermittent 20A for 10 Sec.
Resistance Min. 6Ω @ 35 VDC |
Voltage Regulation
|
< ±0.5% (with 4% engine governing)
|
< ±0.5% (with 4% engine governing)
|
Voltage Build-up
|
Residual volts at AVR terminal > 5 VAC
|
Residual volts at AVR terminal > 5 VAC
|
External Volts Adjustment
|
±5% with 2 KΩ 1 watt trimmer
|
±5% with 2 KΩ 1 watt trimmer
|
CT Current Compensation Input
|
1A or 5A (Selectable)
|
1A or 5A (Selectable)
|
Analogue Input
|
±5 VDC ±10% AC @ ±3 VDC
|
±5 VDC ±10% AC @ ±3 VDC
|
Unit Power Dissipation
|
Max. 10 watt
|
Max. 10 watt
|
Thermal Drift
|
0.03% per °C change in AVR ambient
|
0.03% per °C change in AVR ambient
|
Under Frequency Protection
|
55 Hz @ 60 Hz , 45 Hz @ 55 Hz (Adjustable)
|
320 Hz (Adjustable)
|
Environment
|
Operating Temperature : -40~70 °C
Storage Temperature : -40~85 °C Relative Humidity : Maximum 95% Vibration : 3.3G @ 100~2 KHz |
Operating Temperature : -40~70 °C
Storage Temperature : -40~85 °C Relative Humidity : Maximum 95% Vibration : 3.3G @ 100~2 KHz |
AVR Controls Functions
|
VOLT : Voltage Adjustment
STAB : Stability Adjustment U/F : To Set the U/F* Knee Point (*U/F: Under Frequency Protection) DROOP : To Adjust Droop TRIM : Analogue Input Adjustment |
VOLT : Voltage Adjustment
STAB : Stability Adjustment U/F : To Set the U/F* Knee Point (*U/F: Under Frequency Protection) DROOP : To Adjust Droop TRIM : Analogue Input Adjustment |
Dimensions
|
156.0 (L) x 106.0 (W) x 41.0 (H) mm
|
156.0 (L) x 106.0 (W) x 41.0 (H) mm
|
Weight
|
750 g ±2%
|
750 g ±2%
|