Power Input 
Configuration1-phase or 3-phase
Frequency50 to 400 Hz
Voltage Range 
AVC63-1290 TO 153 Vac
AVC125-10180 to 264 Vac
Maximum Continuous Burden 
AVC63-121,092 VA
AVC125-101,750 VA
See Options for Inrush Current Reduction 
Module information 
Sensing Input  
Configuration1-phase or 3-phase
Burden<1 VA per phase
Voltage Range 
Option A90 to 139 Vac
Option B180 to 264 Vac
Nominal Frequency 
Option 150 or 60 Hz
Option 2400 Hz
Accessory Input 
oltage Range±3 Vdc
Power Output 
Maximum Continuous Output 
AVC63-1212 Adc at 63 Vdc
AVC125-10
10 Adc at 125 Vdc
10 Second Forcing Output 
AVC63-1224 Adc at 125 Vdc
AVC125-1020 Adc at 250 Vdc 
Minimum Field Resistance 
AVC63-125.25 Ω 
AVC125-1012.5 Ω 
Regulation Accuracy±0.5% of voltage setpoint, average response
Voltage Drift±0.5% variation for a 40°C (104°F) change
Response Time <4 ms