AVC 125-10B1 especially made for sensing input 180 to 264 VAC and 50 or 60 HZ frequency, Output voltage range 10 Adc at 125 Vdc. Includes many features and alarms to keep voltage and stability constant and protect the generator in the event of an over excitation.
Power Input | |
Configuration | 1-phase or 3-phase |
Frequency | 50 to 400 Hz |
Voltage Range | |
AVC63-12 | 90 TO 153 Vac |
AVC125-10 | 180 to 264 Vac |
Maximum Continuous Burden | |
AVC63-12 | 1,092 VA |
AVC125-10 | 1,750 VA |
See Options for Inrush Current Reduction | |
Module information | |
Sensing Input | |
Configuration | 1-phase or 3-phase |
Burden | <1 VA per phase |
Voltage Range | |
Option A | 90 to 139 Vac |
Option B | 180 to 264 Vac |
Nominal Frequency | |
Option 1 | 50 or 60 Hz |
Option 2 | 400 Hz |
Accessory Input | |
oltage Range | ±3 Vdc |
Power Output | |
Maximum Continuous Output | |
AVC63-12 | 12 Adc at 63 Vdc |
AVC125-10 |
10 Adc at 125 Vdc
|
10 Second Forcing Output | |
AVC63-12 | 24 Adc at 125 Vdc |
AVC125-10 | 20 Adc at 250 Vdc |
Minimum Field Resistance | |
AVC63-12 | 5.25 Ω |
AVC125-10 | 12.5 Ω |
Regulation Accuracy | ±0.5% of voltage setpoint, average response |
Voltage Drift | ±0.5% variation for a 40°C (104°F) change |
Response Time | <4 ms |